Integral windup
Integral windup, also known as integrator windup or reset windup, refers to the situation in a PID controller where a large change in setpoint occurs (say a positive change) and the integral term accumulates a significant error during the rise (windup), thus overshooting and continuing to increase as this accumulated error is unwound (offset by errors in the other direction).
Solutions
This problem can be addressed by
Occurrence
Integral windup particularly occurs as a limitation of physical systems, compared with ideal systems, due to the ideal output being physically impossible (process saturation: the output of the process being limited at the top or bottom of its scale, making the error constant). For example, the position of a valve cannot be any more open than fully open and also cannot be closed any more than fully closed. In this case, anti-windup can actually involve the integrator being turned off for periods of time until the response falls back into an acceptable range. This usually occurs when the controller's output can no longer affect the controlled variable, or if the controller is part of a selection scheme and it is selected right. Integral windup was more of a problem in analog controllers. Within modern distributed control systems and programmable logic controllers, it is much easier to prevent integral windup by either limiting the controller output, limiting the integral to produce feasible output, or by using external reset feedback, which is a means of feeding back the selected output to the integral circuit of all controllers in the selection scheme so that a closed loop is maintained.
This article is derived from Wikipedia and licensed under CC BY-SA 4.0. View the original article.
Wikipedia® is a registered trademark of the
Wikimedia Foundation, Inc.
Bliptext is not
affiliated with or endorsed by Wikipedia or the
Wikimedia Foundation.