Hard suction hose

1

Flexible suction hose (Flex suction or suction hose), not to be confused with hard suction hose in U.S., is a specific type of fire hose used in drafting operations, when a fire engine uses a vacuum to draw water from a portable water tank, pool, or other static water source. It is built to withstand vacuum, rather than pressure, abrasion, and heat. Conversely, hard suction is capable of withstanding up to 200 PSIG, as well as vacuum. In the United States, it is standard equipment according to the National Fire Protection Association standards for fire engines. It is used in both structural and wildland firefighting throughout the world, and is made in various diameters and connection types.

Usage

Flexible suction hose, also known as a suction hose, is a specific type of rigid fire hose used in drafting operations. When using this technique, the fire engine draws water for fire fighting from an unpressurized supply, such as a portable water tank, pool, or other static water source, instead of drawing water from a pressurized water supply, such as a fire hydrant. Under complete vacuum conditions, a pump would lift water 33.9 ft, however pumps on fire apparatus are not capable of producing a perfect/ total vacuum. Due to this limitation and friction loss, fire services do not recommend attempting to lift water more than 3 m. Hard suction hose may also be used to connect a fire engine to a hydrant, due to its ability to handle both vacuum and pressure. Using hard suction hose in this manner requires that the fire engine be positioned carefully for the limited flexibility of the hose, and may require multiple firefighters due to the weight and bulk of the hose section. The use of flexible suction in this capacity is both ineffective and hazardous, as the hose and couplings may experience catastrophic failure. In certain circumstances, it may be possible to use hard suction hose to draft from a hydrant with adequate water supply but a low flow rate. Flexible suctions are built to withstand vacuum, rather than water pressure, abrasion, and heat. They are, therefore, constructed differently from the standard fire hose and have different end fittings. In the United States, they are standard equipment according to the National Fire Protection Association standards for fire engines. Since neither hard suction nor flexible suction hose can be folded, it is typically mounted on the side of a fire engine, often opposite ground ladders. Such hose is used in both structural and wildland firefighting throughout the world. Hard suction hose can also be used to extend the range of a water tender's dumping capability, if the fittings of the hard suction hose match those of the tender dumping water. This could be used to fill a portable dump tank not immediately adjacent to the water tender, from which another fire engine can draft. Since water movement during dumping relies on gravity, rather than mechanical pressurization, hard suction hose is useful for this task.

Characteristics and construction

Suction hose differs from standard fire hose in both its construction and usage: Hard suction hose predates steam or gas powered fire engines and has been available since at least 1888, sometimes referred to as "spiral suction hose". Modern apparatus are commonly equipped with flexible suction as opposed to hard suction, due to the relative ease of use associated with flexibility, as well as the increasing rarity of employing suction hoses to pressurized water sources.

Diameter

Suction hose comes in multiple sizes, from 2 to 6 in in diameter. Large diameter hose are carried on full-size fire engines, but smaller diameters of hard suction hose can be carried on apparatus with smaller fire pump ratings, such as wildland fire engines. In the United States, NFPA 1901 requires engines to have suction hose that matches the engine's pump rating. For example, an engine with a 1000 USgal per minute pump is required to carry 5 in or larger hose, while a wildland fire engine will typically carry 2 to 2.5 in hard suction hose. The United Kingdom, has a standardised range of metric hose diameters: 7, 9, 12.5 and 15 cm (2.8, 3.5, 4.9 and 5.9 in), with the two smallest diameters sometimes used twinned to provide adequate flow rates. Within this range, the 7 cm hoses are fitted with "Instantaneous Couplings"; the 12.5 and 15 cm hoses have Storz couplings; and the 9 cm hose comes in two types, one with "Instantaneous Couplings" and one with Storz fittings. Fire Service Manuals provide tables of maximum volumetric flow rates for a given pump pressure, hose diameter and total hose length. The use of these tables, is to facilitate the selection of suitable hoses, taking into account the frictional losses caused by transporting water through the strainer, hoses, pump and fire fighting nozzles, to draft water from source to the fireground.

Strainers

When being used in a drafting operation from a pool, portable water tank, or other uncovered water source, the length of suction hose farthest from the pump is usually attached to a strainer, to keep foreign objects in the water from being pulled into and damaging the pump. If used in a pond, stream, or other body of water, an appropriate flotation device must be used to keep the strainer below the surface and above the bottom, so that neither mud nor air are sucked into the fire engine's pump. Industry accepted standard is to maintain two feet of distance from the water's surface, bottom, or any other obstruction. The United Kingdom official guidance is to: